Marine Fire Suppression System >> Gas Type Fire ExtinguishingSystem >> Water Mist Fire Extinguishing System
Water mist fire extinguishing system structure
Product No. MFFE007-WMFE
Item Name Item Name Item Name
(1) Inlet connection (2) Buffer tank (3) Level switch
(4) Pressure relief valve (5) High Pressure Manifold (6) Main valve
(7) Suction manifold (8) Mnometer (9) Pressure transmitter
(10) Test valve (11) Eletric motor (12) Pilot pump
(13) Redundant pump (14) High pressure pump    
(15) Non-return valve (16) Eletric motor    
Standard
  It is designed and installed in accordance with applicable SOLAS guidelines based on IMO Resolution A.800(19), as well as the design parameters established pursuant to the IMO-MSC/Circ. 1165.Typical ship types where it can be used include cruise ships, ferries and large yachts.
Applications
  Accommodation, public space and store areas A single Watfire sprinkler will provide coverage of up to 32 Μ² in these areas. That means the sprinklers can be installed at six-metre intervals on corridors - in total, the Watfire system requires far fewer sprinklers than standard systems, which also simplifi es ceiling design.
Main technical parameters
Model Nominal pressure(Mpa) Rated flow (L/min) Nominal rated power (KW) voltage frequency (V/Hz) start method Ambient Temperature
ZSXZB40/3.5 3.5 40 3 380V/50Hz 400V/50Hz 400V/60Hz 415V/50Hz 415V/60Hz 440V/60Hz automatic,Electrical manual,manual emergency operation
4-50
ZSXZB80/3.5 80 5.5
ZSXZB120/3.5 120 7.5
ZSXZB160/3.5 160 11
ZSXZB250/3.5 250 18.5
ZSXZB360/3.5 360 30
ZSXZB450/3.5 450 30
ZSXZB550/3.5 550 37
Model flow coefficient K minimum working pressure maximum working pressure maximum horizontal spacing Distance protection content minimum vertical height Distance protection content maximum vertical height
ZSXTC60-9 5.96 2 3.5 2.5 2 12
ZSXTC60-9-A 5.96 2 3.5 2.5 0.5 2

Click here to contact me!