| Product No. |
MFFE007-WMFE |
| Item |
Name |
Item |
Name |
Item |
Name |
| (1) |
Inlet connection |
(2) |
Buffer tank |
(3) |
Level switch |
| (4) |
Pressure relief valve |
(5) |
High Pressure Manifold |
(6) |
Main valve |
| (7) |
Suction manifold |
(8) |
Mnometer |
(9) |
Pressure transmitter |
| (10) |
Test valve |
(11) |
Eletric motor |
(12) |
Pilot pump |
| (13) |
Redundant pump |
(14) |
High pressure pump |
|
|
| (15) |
Non-return valve |
(16) |
Eletric motor |
|
|
| Standard |
| |
It is designed and installed in accordance with applicable SOLAS guidelines based on IMO Resolution A.800(19), as well as the design parameters established pursuant to the IMO-MSC/Circ. 1165.Typical ship types where it can be used include cruise ships, ferries and large yachts. |
| Applications |
| |
Accommodation, public space and store areas A single Watfire sprinkler will provide coverage of up to 32 Μ² in these areas. That means the sprinklers can be installed at six-metre intervals on corridors - in total, the Watfire system requires far fewer sprinklers than standard systems, which also simplifi es ceiling design. |
| Main technical parameters |
| Model |
Nominal pressure(Mpa) |
Rated flow (L/min) |
Nominal rated power (KW) |
voltage frequency (V/Hz) |
start method |
Ambient Temperature |
| ZSXZB40/3.5 |
3.5 |
40 |
3 |
380V/50Hz 400V/50Hz 400V/60Hz 415V/50Hz 415V/60Hz 440V/60Hz |
automatic,Electrical manual,manual emergency operation
|
4-50 |
| ZSXZB80/3.5 |
80 |
5.5 |
| ZSXZB120/3.5 |
120 |
7.5 |
| ZSXZB160/3.5 |
160 |
11 |
| ZSXZB250/3.5 |
250 |
18.5 |
| ZSXZB360/3.5 |
360 |
30 |
| ZSXZB450/3.5 |
450 |
30 |
| ZSXZB550/3.5 |
550 |
37 |
| Model |
flow coefficient K |
minimum working pressure |
maximum working pressure |
maximum horizontal spacing |
Distance protection content minimum vertical height |
Distance protection content maximum vertical height |
| ZSXTC60-9 |
5.96 |
2 |
3.5 |
2.5 |
2 |
12 |
| ZSXTC60-9-A |
5.96 |
2 |
3.5 |
2.5 |
0.5 |
2 |