Marine Fire Suppression System >> FM-200 Fire Extinguishing System >> FM-200 Fire Extinguishing System
FM200
Porduct No. MFFE007-FM200
Main Technical Parameters
Standard Q/HF123-2007
System performance fixed,total flooding type,fire extinguishing agent injection time ≤10S
Operation mode Pneumatic remote control operation or manual mechanical(Operating Force≤98N)
Environmental condition ambient temperature -10℃-50℃
relative temperature 93±3%
Power supply main power source AC220V 50Hz
Auxiliary power supply DC24V 3A
Storage device performance
  Storage container volume(L) 40、70、90、100、120、150、180
Fire extinguishing agent filling rate(kg/m3) ≤1120
storage pressure(20℃) 4.2MPa
MWP(maximum working pressure)(50℃) 6.7MPa
start method remote operation & manual mechanical
Remote control release station performance
  Storage container volume(L) 4
storage pressure (20℃) 6.0MPa
Pneumatic time-delay device delay time 20S-40S
start method manual mechanical
Pneumatic cast valve performance
  Nominal pressure(mm) 25、32、40、50、65、80、100、125、150
Working pressure(MPa) 10.0MPa
Start method remote operation & manual mechanical
additional function Equipped with stroke switch, provide a normally open and a normally closed contacts
The agent would extinguish following fire
  electric fire
liquid fire or melting solid fire
solid surface fire
gas fire that the gas would be elimilated before fire extinguishing
Mairne fire extinguishing system could be placed in the shipping engine room,pump cabin, hold,oil cabin,generate electricity room,paint room,woodworker room, kitchen and so on.